Power Factor Correction

The Power Factor Correction of electrical loads is a problem common to all industrial companies. Every user which utilizes electrical power to obtain work in various forms continuously asks the mains to supply a certain quantity of active power together with reactive power. Most loads on an electrical distribution system can be placed in one of three categories.

  • Resistive
  • Inductive
  • Capacitive

The most common of these on modern systems is the inductive load. Typical examples includes transformer, fluorescent lighting, AC induction motors, Arc/induction, furnaces etc. which draw not, only active power from the supply, but also inductive reactive power (KVAr). Common characteristics of these inductive loads is that they utilize a winding to produce an electromagnetic field which allows the motor or transformer to function and requires certain amount of electrical power in order to maintaining the field. Therefore Active Power (KW) actually performs the work whereas Reactive Power (KVAr) sustain the electro-magnetic field. This reactive power though is necessary for the equipment to operate correctly but could be interpreted as an undesirable burden on the supply.

Power Factor (Cosφ )

The power factor Cosφ of a load is defined as the ratio of active power to apparent power i.e.

Apparent power is combination of reactive & active power. The closer cosφ is to unity, the less reactive power is drawn from the supply. 
                                             

Power Factor Correction of Electrical loads

 

Install a Power Factor Correction System?

There are many objectives to be pursued in the planning of an electrical system. In addition to safety and reliability, it is very important to ensure that electricity is properly used. Each circuit, each piece of equipment, must be designed so as to guarantee the maximum global efficiency in transforming the source of energy into work.

Among the measures that enable electricity use to be optimized, improving the power factor of electrical systems is undoubtedly one of the most important.

If we quantify this aspect from the utility company’s point of view, raising the average operating power factor of the network from 0.7 to 0.9 means:

  •  cutting costs due to ohmic losses in the network by 40%

  •  increasing the potential of production and distribution plants by 30%.
     

These figures speak for themselves: it means saving hundreds of thousands of tons of fuel and making several power plants and hundreds of transformer rooms available.

Thus in the case of low power factors utility companies charge higher rates in order to cover the additional costs they must incur due to the inefficiency of the system that taps energy.

It is a well-known fact that electricity users relying on alternating current – with the exception of heating elements – absorb from the network not only the active energy they convert into mechanical work, light, heat, etc. but also an inductive reactive energy whose main function is to activate the magnetic fields necessary for the functioning of electric machines.

The power factor is thus the ratio between active power and apparent power (vectorial sum of active and reactive power), an indicator of the quality of a facility’s electric system since the lower the power factor is, the higher the inductive reactive component will be in relation to the active component.

It is possible to produce reactive energy, where necessary, by installing power capacitors or automatic power factor correction systems. Capacitors absorb a current that is 180% out of phase with the inductive reactive current; the two currents are algebraically summed together so that circulating upstream from the point of installation of the capacitor is a reactive current that is equal to the difference between the inductive and capacitive currents.

The exchange occurs between the capacitor and user; this is why we say that the capacitor supplies reactive energy to the user.

Power flows with and without power factor correction

 

Power flows with and without power factor correction
 

Theoretically speaking, when you must choose where to locate the capacitive power the most appropriate solution from a technical standpoint would be to assign each load its own power factor correction capacitor, to be switched on together with the machine.

In practice, however, this entails excessive costs and technical problems in most cases, since it requires the installation of a larger number of low-power capacitors distributed in many different points, which cannot be effectively monitored over time; plus little benefit is to be derived from reducing losses in the cables, negligible compared to those in the power transformer. Therefore, this solution is only feasible in large facilities or where there are very high power loads.
                            

Automatic System of The Capacitor Bank

The most appropriate power factor correction system thus consists in the installation of an automatic capacitor bank on the bus bars of the distribution panel and, if necessary, fixed capacitor banks for correcting the power factor of the transformer, asynchronous motors and any loads absorbing considerable quantities of reactive power.

The automatic system of the capacitor bank has the task of switching in the necessary capacitance according to the load requirements at each given moment.

 

Choice & Calculation

Choice & Calculation of The Power Factor Correction?

Calculating the dimensions of the capacitor bank you need to install in your system is very simple: note the cos of the system without power factor correction and the cos you want to obtain and it will take just a few calculations to derive the reactive power necessary in order to reach the desired power factor. The power factor can differ greatly between two users because it depends both on the type of equipment installed and how it is used.

For example, asynchronous motors – by far the most widely used, though brushless motors actuated by static AC/DC or AC/AC converters have been gaining popularity in recent years – have a power factor that varies greatly according to the motor load and type of construction and can reach very low values in the absence of loads. Similar observations may be made with respect to transformers. For all these types of electric machines, recourse is often made to a fixed power factor correction at the motor or transformer level. Other significant differences can be seen in electrical equipment such as lamps, furnaces, welding machines and converters.

Calculating of reactive power necessary power factor correction

P           =  active power of the system
cosφ0 = cosφ of system without power factor correction
cosφ1 = cosφ you want to bring the system to
Qc      = reactive power of power factor correction system to be installed
k        =
cosφ0 and cosφ1, this data is derived from the table (next page)
Qc     = P(tanφ0 - tanφ1) =P.K

Correcting the Power Factor of MV / LV Transformers


It is always a good idea to ensure a power factor correction for MV / LV transformers, since even when they are operating loadless (e.g. during the night) they absorb reactive power, which must be compensated. The exact capacitor power necessary may be calculated using the formula below:
Q = Io% * Pn / 100
Io = loadless current (specified by the transformer manufacturer)
Pn = rated power of the transformer

Where alternatively, if the required data is not available, you can refer to the table below, which differentiates among types of transformers with NORMAL losses.

Reactive power for CORRECTING the POWER FACTOR CORRECTION NO LOAD of 50hz three phase transformation MV/LV(kvar)

Choice & Calculation of The Power Factor Correction

 

Real Time Power Factor Correction

Real Time Power Factor Correction (Activcomp) and What are Its Advantages ?

General information

Modern manufacturing plants are characterized by the use of highly dynamic machinery, like welding loads. Alongside the undisputed advantages of today’s modern techniques there is however the disadvantage that the mains supply networks are often affected by frequent load fluctuations and harmonic oscillation. It often leads to unstable stress ratios. Flickering, excessive current and increased losses in energy distribution. This reduces not only the supply capacity but also impairs the function of sensitive electronics controls.

Conventional reactive power compensation systems are designed for optimizing the power factor and reducing the level of harmonic oscillation, but offer no satisfactory solution for frequent load fluctuations. The range of application of these units is the compensation of static as well as fluctuating loads with switching cycles measured by minutes.

  • At each moment optimized cosφ
  • Soft switching without transients
  • Flicker eliminated
Application
 

The real-time power factor compensation equipment of series Activcomp offers a solution. In these assemblies the classic components controller and air contactor are substituted by a combination of corresponding high speed controller and thyristor power modules type Activcomp . This system reacts immediately on load fluctuation and reactive power surges will be neutralised in the supply network. The power factor is optimised at each moment, on cycle to cycle basis, typical response time less than 20 ms. The negative effects described above are reduced to a minimum. This gives the consumer not only the advantage of a stable supply ratio, but the ability to minimise energy distribution and reduce costs. To increase the switching performance to an optimum, the control signal for the steering of the capacitor banks can alternatively be given directly by the logic control of bigger loads.

 Real-time Power Factor Compensation Systems


Coefficient k by which to multiply the active energy consumed in KW in order to determine the KVAR necessary for correcting the power factor
(Cosφ1 is the initial PF obtainable with correction),
Recommender final
Cosφ = 0.95 upto1.00

Coefficient K
Value Cosφ

Tgφ

Cosφ

0.85 0,86 0,87 0,88 0,89 0,90 0,91 0,92 0,93 0,94 0,95 0,96 0,97 0,98 0,99 1,00
3,18 0,30 2,560 2,586 2,613 2,640 2,667 2,695 2,754 2,754 2,785 2,817 2,851 2,888 2,929 2,977 3,037 3,180
3,0 0,31 2,447 2,474 2,500 2,527 2,555 2,583 2,611 2,641 2,672 2,704 2,738 2,775 2,816 2,864 2,924 3,067
2,96 0,32 2,341 2,367 2,394 2,421 2,448 2,476 2,505 2,535 2,565 2,598 2,632 2,669 2,710 2,758 2,818 2,961
2,86 0,33 2,241 2,267 2,294 2,321 2,348 2,376 2,405 2,435 2,465 2,498 2,532 2,569 2,610 2,657 2,718 2,861
2,77 0,34 2,146 2,173 2,199 2,226 2,254 2,282 2,310 2,340 2,371 2,403 2,437 2,474 2,515 2,563 2,623 2,766
2,68 0,35 2,057 2,083 2,110 2,137 2,164 2,192 2,221 2,250 2,281 2,313 2,348 2,385 2,426 2,473 2,534 2,676
2,59 0,36 1,972 1,998 2,025 2,052 2,079 2,107 2,136 2,166 2,196 2,229 2,263 2,300 2,341 2,388 2,449 2,592
2,51 0,37 1,891 1,918 1,994 1,971 1,999 2,027 2,055 2,085 2,116 2,148 2,187 2,219 2,260 2,308 2,368 2,511
2,43 0,38 1,814 1,841 1,867 1,894 1,922 1,950 1,979 2,008 2,039 2,071 2,105 2,143 2,184 2,231 2,292 2,434
2,36 0,39 1,741 1,768 1,794 1,821 1,849 1,877 1,905 1,935 1,966 1,998 2,032 2,069 2,110 2,158 2,219 2,361
2,29 0,40 1,672 1,698 1,725 1,752 1,779 1,807 1,836 1,865 1,896 1,928 1,963 2,000 2,041 2,088 2,149 2,291
2,22 0,41 1,605 1,631 1,658 1,685 1,712 1,740 1,796 1,799 1,829 1,862 1,896 1,933 1,974 2,022 2,082 2,225
2,16 0,42 1,514 1,567 1,594 1,621 1,648 1,676 1,705 1,735 1,766 1,798 1,832 1,869 1,910 1,958 2,018 2,161
2,10 0,43 1,480 1,506 1,533 1,560 1,587 1,615 1,644 1,674 1,704 1,737 1,771 1,808 1,849 1,897 1,957 2,100
2,04 0,44 1,421 1,448 1,474 1,501 1,526 1,557 1,585 1,615 1,646 1,678 1,712 1,749 1,790 1,838 1,898 2,041
1,98 0,45 1,365 1,391 1,418 1,445 1,472 1,500 1,529 1,559 1,589 1,622 1,656 2,693 1,734 1,781 1,842 1,985
1,93 0,46 1,311 1,337 1,364 1,391 1,418 1,446 1,475 1,504 1,535 1,567 1,602 1,639 1,680 1,727 1,788 1,930
1,88 0,47 1,258 1,285 1,311 1,338 1,366 1,394 1,422 1,452 1,483 1,515 1,549 1,.586 1,627 1,675 1,736 1,878
1,83 0,48 1,208 1,234 1,261 1,288 1,315 1,343 1,372 1,402 1,432 1,456 1,499 1,536 1,577 1,625 1,685 1,828
1,78 0,49 1,159 1,189 1,212 1,239 1,267 1,295 1,323 1,353 1,384 1,416 1,450 1,487 1,528 1,576 1,637 1,779
1,73 0,50 1,112 1,139 1,165 1,192 1,220 1,248 1,276 1,306 1,337 1,369 1,403 1,440 1,481 1,529 1,590 1,732
1,69 0,51 1,067 1,093 1,120 1,147 1,174 1,202 1,231 1,261 1,391 1,324 1,358 1,395 1,436 1,484 1,544 1,687
1,64 0,52 1,023 1,049 1,079 1,103 1,130 1,158 1,187 1,217 1,247 1,280 1,314 1,351 1,392 1,440 1,500 1,643
1,60 0,53 0,980 1,007 1,033 1,060 1,088 1,116 1,144 1,174 1,205 1,237 1,271 1,308 1,349 1,397 1,458 1,600
1,56 0,54 0,939 0,965 0,992 1,019 1,046 1,074 1,103 1,133 1,163 1,196 1,230 1,267 1,308 1,356 1,416 1,556
1,52 0,55 0,899 0,925 0,952 0,979 1,006 1,034 1,063 1,092 1,123 1,156 1,190 1,227 1,268 1,315 1,376 1,518
1,48 0,56 0,860 0,886 0,913 0,940 0,967 0,995 1,024 1,053 1,084 1,116 1,151 1,188 1,229 1,276 1,337 1,476
1,44 0,57 0,822 0,848 0,875 0,902 0,926 0,957 0,986 1,015 1,046 1,079 1,113 1,150 1,191 1,.238 1,299 1,441
1,40 0,58 0,785 0,811 0,838 0,865 0,892 0,920 0,949 0,979 1,009 1,042 1,076 1,113 1,154 1,201 1,262 1,405
1,37 0,59 0,749 0,775 0,802 0,829 0,56 0,884 0,913 0,942 0,973 1,006 1,040 1,077 1,118 1,165 1,226 1,368
1,33 0,60 0,714 0,740 0,767 0,794 0,821 0,849 0,878 0,907 0,938 0,970 1,005 1,042 1,083 1,130 1,191 1,333
1,30 0,61 0,679 0,706 0,732 0,759 0,787 0,815 0,843 0,873 0,904 0,936 0,970 1,007 1,048 1,096 1,157 1,299
1,27 0,62 0,646 0,672 0,699 0,726 0,753 0,781 0,810 0,839 0,870 0,903 0,937 0,374 1,015 1,062 1,123 1,265
1,23 0,63 0,613 0,639 0,666 0,693 0,720 0,748 0,777 0,807 0,837 0,870 0,904 0,941 0,982 1,030 1,090 1,233
1,20 0,64 0,581 0,607 0,634 0,661 0,688 0,.716 0,745 0,775 0,805 0,838 0,872 0,909 0,950 0,998 1,058 1,201
1,17 0,65 0,549 0,579 0,602 0,629 0,657 0,685 0,714 0,743 0,774 0,806 0,840 0,877 0,919 0,966 1,027 1,169
1,14 0,66 0,519 0,545 0,572 0,599 0,626 0,654 0,683 0,712 0,743 0,775 0,810 0,847 0,888 0,935 0,996 1,138
1,11 0,67 0,488 0,515 0,541 0,568 0,596 0,624 0,652 0,682 0,713 0,.745 0,779 0,816 0,857 0,905 0,966 1,108
1,08 0,68 0,459 0,485 0,512 0,539 0,566 0,594 0,623 0,652 0,683 0,715 0,750 0,787 0,828 0,875 0,936 1,078
1,05 0,69 0,429 0,456 0,482 0,509 0,537 0,565 0,593 0,623 0,654 0,686 0,702 0,57 0,798 0,846 0,907 1,049
1,02 0,70 0,400 0,427 0,453 0,480 0,508 0,539 0,565 0,594 0,625 0,.657 0,692 0,729 0,770 0,817 0,878 1,020
0,99 0,71 0,372 0,398 0,425 0,452 0,480 0,508 0,536 0,566 0,597 0,629 0,663 0,700 0,714 0,789 0,849 0,992
0,96 0,72 0,344 0,370 0,397 0,424 0,452 0,480 0,508 0,538 0,569 0,601 0,635 0,672 0,713 0,761 0,821 0,964
0,94 0,73 0,316 0,343 0,370 0,396 0,424 0,452 0,481 0,510 0,541 0,.573 0,608 0,645 0,686 0,733 0,794 0,936
0,91 0,74 0,289 0,316 0,342 0,369 0,397 0,425 0,453 0,483 0,514 0,546 0,580 0,617 0,658 0,706 0,766 0,909
0,88 0,75 0,262 0,289 0,315 0,342 0,370 0,398 0.,426 0,456 0,487 0.,519 0,553 0,590 0,631 0,679 0,739 0,882
0,86 0,76 0,235 0,262 0,288 0,315 0,343 0,371 0,400 0,429 0,460 0,492 0,526 0,563 0,605 0,652 0,713 0,855
0,83 0,77 0,209 0,235 0,262 0,289 0,316 0,344 0,373 0,403 0,433 0,466 0,500 0,537 0,578 0,626 0,686 0,829
0,80 0,78 0,183 0,209 0,236 0,263 0,290 0,318 0,347 0,376 0,407 0,439 0,474 0,511 0,552 0,599 0,660 0,.802
0,78 0,79 0,156 0,183 0,209 0,236 0,264 0,292 0,320 0,350 0,381 0,413 0,447 0,484 0,525 0,573 0,634 0,776
0,75 0,80 0,130 0,157 0,183 0,210 0,238 0,266 0,294 0,324 0,355 0,387 0,421 0,458 0,499 0,547 0,608 0,750
0,72 0,81 0,104 0,131 0,157 0,184 0,212 0,240 0,268 0,298 0,329 0,361 0,395 0,432 0,473 0,521 0,581 0,724
0,70 0,82 0,078 0,105 0,131 0,158 0,186 0,214 0,242 0,272 0,303 0,335 0,369 0,406 0,447 0,495 0,556 0,698
0,67 0,83 0,052 0,079 0,105 0,132 0,160 0,188 0,216 0,246 0,277 0,309 0,343 0,380 0,421 0,469 0,530 0,672
0,65 0,84 0,029 0,053 0,079 0,106 0,134 0,162 0,190 0,220 0,251 0,283 0,317 0,354 0,395 0,443 0,503 0,646
0,62 0,85   0,026 0,053 0,080 0,107 0,135 0,164 0,194 0,225 0,257 0,291 0,328 0,369 0,417 0,477 0,620
0,59 0,86     0,027 0,054 0,081 0,109 0,138 0,167 0,198 0,230 0,265 0,302 0,343 0,390 0,451 0,593
0,57 0,87       0,027 0,054 0,082 0,111 0,141 0,172 0,204 0,238 0,275 0,316 0,364 0,424 0,567
0,54 0,88         0,027 0,055 0,084 0,114 0,145 0,177 0,211 0,248 0,289 0,337 0,397 0,540
0,51 0,89           0,028 0,057 0,086 0,117 0,149 0,184 0,221 0,262 0,309 0,370 0,512
0,48 0,90             0,029 0,058 0,089 0,121 0,156 0,193 0,234 0,281 0,342 0,484
0,46 0,91               0,030 0,060 0,093 0,127 0,.164 0,205 0,253 0,313 0,456
0,43 0,92                  0,031 0,063 0,097 0,134 0,175 0,223 0,284 0,426
0,46 0,93                   0,032 0,067 0,104 0,145 0,192 0,253 0,395
0,36 0,94                     0,034 0,071 0,.112 0,160 0,220 0,363
0,33 0,95                        0,037 0,078 0,126 0,186 0,329
0,29 0,96                                    0,041s 0,089 0,149 0,292
0,25 0,97                                               0,048 0,108 0,251
0,20 0,98                                              0,061 0,203
0,14 0,99                                  0.142


 

Advantages of Thyristor Switched

Advantages of Thyristor Switched Over Electro-Mechanical Compensation System ?



Fast and Accurate Compensation

The Activcomp is a Transient Free Fast Compensation System. It is used for Power Factor Correction & Harmonic Filter. The compensation is based on averaging the FFT analysis of each cycle, resulting in more accurate compensation, even in the presence of harmonics.

Simultaneous Group Connection

When load changes require connection or disconnection of more than one step, the Activcomp controls the switching of as many steps as required at precisely the same time. Simultaneous connection or disconnection provides the following benefits :

• Fast full compensation.
• For Eg., with 1:2:2 system configuration and groups 1 & 2 are connected. When 1 more step is required, group 3 will 
  be connected simultaneously while group 1 is disconnected.
• Real binary sizing - 1:2:2 is exactly the same as 1:1:1:1:1.

Transient-free Switching

Electronic switching technology prevents any transients typically associated with conventional capacitor switching. This is extremely important in sites with sensitive electronic equipment, such as hospitals, data centers and facilities.

Fixed Capacity & Filter Characteristics

The capacity of the Activcomp capacitors is virtually permanent over the years, which prevents the need to replace capacitors. Moreover the tuning frequency remains constant over time, which allows system performance to remain at the highest possible level.

There is an ongoing cumulative reduction of capacity in electro mechanically switched PFC systems due to the effect of transients during connections and disconnection. This can be detrimental to detuned electro mechanically switched systems where the changes in ratio between the capacitors/reactors shift the resonance frequency, which may result in resonance. The Activcomp prevents these conditions.

Long Life and Reduced Maintenance Costs

Neptune Activcomp reduces site maintenance costs by increasing the lifetime of:
• Switching elements
• Capacitors
• Sensitive electronic equipment

Capacitor Duty Cycle-SCAN Mode

The unique SCAN feature protects the Activcomp’s capacitors & reactors, increases their life span. Simultaneous connection and disconnection of steps in FIFO (First In First Out) manner is shown in diagram on the previous page.

The scan feature reduces the average current in the capacitors and the reactors and therefore providing the following advantages:

• Reduces substantially the increase of temperature in these elements resulting in longer life expectancy of the
   inductors and capacitors.
• Reduces the effect of over-current and over voltage caused by the harmonics on the capacitors and inductors.
• The tuning frequency of the de-tuned filter or tuned filter is stable due to the fact that the capacitor  value (micro farad) 
  doesn't change due to the low temperature achieved by the scan mode.

Easy to Use and Maintain

The advanced DSP and microprocessor-based controller, with its large full graphic LCD display, provides easy-to-use operation. The controller includes a complete electrical measurement system, which can replace a facilities main monitoring meter. The controller operates the BIT (Built In Test), which reports system or network conditions. The optional PowerlQ software can remotely control all Activcomp operation and display additional system power information.

 

 

Power Factor Corrections Capacitors

Power Factor Corrections Capacitors.

Unlike most electrical equipment, power factor correction capacitors, each time they are energized, continuously operate at full load or at loads which differ from this value only as a consequence of variations in voltage and frequency.

Overstressing and overheating shorten the life span of the capacitor. For this reason the operating conditions (temperature, voltage and current) must be carefully controlled in order to obtain optimum results as respects the lifespan of the capacitor.

Voltage
The capacitors are produced in accordance with reference standards EN 60831-1/2 which regulate their manufacturing, testing, installation and application and which indicate the following maximum values for over voltage applicable to the capacitors:

+10% for 8 hours every 24 hours
+15% for 30 minutes every 24 hours
+20% for 5 minutes every 24 hours
+30% for 1 minute every 24 hours.

Over voltages in excess of 15% should not occur more than 200 times in the lifespan of the capacitor. Often when there is the presence of overload conditions during service, in the presence of a moderate harmonic load for example, it is common to use oversized capacitors in terms of voltage.
 

                        

In such cases the output power at operating voltage will be reduced with respect to that of the rated load. It is advisable to evaluate the reduction experienced in the output power on the basis of the correlation between the operating voltage and the rated voltage.

The following table indicates the output power of a 100 kvar capacitor used on a 400 V network with a rated voltage of 450 V, 500 V  and 550 V.
 

 Un     450    500  550
 Q output kvar      79     64   53

                                              

Temperature

The temperature of the capacitor during operation is the parameter that, along with the voltage, has the greatest influence on the life span of the capacitor. It is important that the capacitor always be placed in a position where the cooling air can freely circulate, avoiding the radiant heat of hot surfaces of other components. When the capacitors are placed in closed cabinets it is necessary to have air vents which allow for an easy exchange of air between the interior and exterior of the cabinet. On the other hand, when the degree of protection of the cabinet does not permit this exchange of air, the internal spaces must be much larger and the positioning of the capacitors must be carefully studied to permit the necessary channels which allow for the circulation of cooling air. In this case the forced cooling air will have to be provided by suitable fans. As a rule the temperature of the cooling air inside the cabinet should not differ by more than
5ºC with respect to the external air at the control panel.

Cooling air temperature

This is the temperature of cooling air measured at the hottest point of the bank of capacitors, under working conditions, halfway between two capacitors or on the surface of one of these.

Categories of ambient air temperature

This represents the range of cooling air temperatures in which the capacitor is designed to operate. As a rule there are 4 categories represented by a number and a letter or by two numbers as shown in the table.
 

Categories                           Ambient air temperature
   

Max

   Highest mean over any period of

24h 1year
-25/A

-25+40°C.

      40           40         40
-25/B -25+45°C       45           35         35
-25/c -25+50°C       50           40         40
-25/D -25+55°C       55           45         35


The first number represents the minimum temperature of the cooling air at which the capacitor can be energized (-
25ºC) on request -40ºC. The letter or the second number represents the upper limit of the temperature range and precisely the max. value indicated in the table.

Residual voltage

This is the voltage that remains after disconnecting the capacitor from the network. This voltage must be eliminated in order to avoid dangerous conditions for the operator. All three-phase capacitors are equipped with discharge devices, that reduce the residual voltage to a value of minimum 75 V after 3 minutes.

It is important to bear in mind that the capacitors cannot be energized if there is a residual voltage of more than 10% across them. Particular attention must therefore be applied in harmonizing the capacitor discharge times with the response times of the control devices (Regulators). In cases where the lag time of the regulators are shorter than the discharge time of the capacitor, it is necessary to provide additional discharge devices until the connection occurs with a residual voltage of less than 10%.

To reduce the residual voltage to 50 V in 20 seconds in batteries with a power less than or equal to 20 kvar at a voltage of 400 V, use 3 metal oxide resistors of 68 kohm, 4W in a delta connection.

Max current

The capacitors are made to function conforming to standards EN 60831 - 1/2 continuously at an effective value at last of 1.3 times the value of the current at rated voltage and frequency. Bearing in mind the capacitance tolerance, the maximum current can arrive to 1.5 In, the value to which it is necessary to refer in the scaling of the line of control and protection devices. This overcurrent factor can be determined by the combined effect of harmonics, overvoltages and capacitance tolerance.

Max inrush current

Transient overcurrents having elevated amplitudes and high frequencies occur when the capacitors are switched in to the circuit. This is especially true when a bank of capacitors are put in a parallell connection with other already-energized capacitors. It may therefore be necessary to reduce these transient overcurrents to acceptable values both for the capacitor and the contactor used by connecting the capacitor using suitable devices (resistors or reactors) in the power circuit of the battery. The peak value of the overcurrent caused during maneuvering operations must be limited to a maximum value of 100 In (crest value of the 1st cycle).