 |
The Power Factor Correction of electrical loads is a problem common to
all industrial companies. Every user which utilizes electrical power
to obtain work in various forms continuously asks the mains to supply
a certain quantity of active power together with reactive power. Most
loads on an electrical distribution system can be placed in one of
three categories.
- Resistive
- Inductive
- Capacitive
The most common of these on modern systems is the inductive load.
Typical examples includes transformer, fluorescent lighting, AC
induction motors, Arc/induction, furnaces etc. which draw not, only
active power from the supply, but also inductive reactive power (KVAr).
Common characteristics of these inductive loads is that they utilize a
winding to produce an electromagnetic field which allows the motor or
transformer to function and requires certain amount of electrical
power in order to maintaining the field. Therefore Active Power (KW)
actually performs the work whereas Reactive Power (KVAr) sustain the
electro-magnetic field. This reactive power though is necessary for
the equipment to operate correctly but could be interpreted as an
undesirable burden on the supply.
Power Factor (Cosφ )
The power factor Cosφ of a load is defined as the ratio of active
power to apparent power i.e.

Apparent power is combination of reactive & active power. The closer
cosφ is to unity, the less reactive power is drawn from the
supply.
|
 |
|
|
 |
Install a Power Factor
Correction System?
There are many objectives to be pursued in the planning of an
electrical system. In addition to safety and reliability, it is very
important to ensure that electricity is properly used. Each circuit,
each piece of equipment, must be designed so as to guarantee the
maximum global efficiency in transforming the source of energy into
work.
Among the measures that enable electricity use to be optimized,
improving the power factor of electrical systems is undoubtedly one of
the most important.
If we quantify this aspect from the utility company’s point of view,
raising the average operating power factor of the network from 0.7 to
0.9 means:
|
|
|
These figures speak for themselves: it means saving hundreds of
thousands of tons of fuel and making several power plants and hundreds
of transformer rooms available.
Thus in the case of low power factors utility companies charge higher
rates in order to cover the additional costs they must incur due to
the inefficiency of the system that taps energy.
It is a well-known fact that electricity users relying on alternating
current – with the exception of heating elements – absorb from the
network not only the active energy they convert into mechanical work,
light, heat, etc. but also an inductive reactive energy whose main
function is to activate the magnetic fields necessary for the
functioning of electric machines.
The power factor is thus the ratio between active power and apparent
power (vectorial sum of active and reactive power), an indicator of
the quality of a facility’s electric system since the lower the power
factor is, the higher the inductive reactive component will be in
relation to the active component.
It is possible to produce reactive energy, where necessary, by
installing power capacitors or automatic power factor correction
systems. Capacitors absorb a current that is 180% out of phase with
the inductive reactive current; the two currents are algebraically
summed together so that circulating upstream from the point of
installation of the capacitor is a reactive current that is equal to
the difference between the inductive and capacitive currents.
The exchange occurs between the capacitor and user; this is why we say
that the capacitor supplies reactive energy to the user.
|
|
|
|
Power flows with and without power factor
correction
|
|
Theoretically speaking, when you must choose where to locate the
capacitive power the most appropriate solution from a technical
standpoint would be to assign each load its own power factor
correction capacitor, to be switched on together with the machine.
In practice, however, this entails excessive costs and technical
problems in most cases, since it requires the installation of a larger
number of low-power capacitors distributed in many different points,
which cannot be effectively monitored over time; plus little benefit
is to be derived from reducing losses in the cables, negligible
compared to those in the power transformer. Therefore, this solution
is only feasible in large facilities or where there are very high
power loads.
|
|
The most appropriate power factor correction system thus consists in
the installation of an automatic capacitor bank on the bus bars of the
distribution panel and, if necessary, fixed capacitor banks for
correcting the power factor of the transformer, asynchronous motors
and any loads absorbing considerable quantities of reactive power.
The automatic system of the capacitor bank has the task of switching
in the necessary capacitance according to the load requirements at
each given moment.
|
 |
Choice & Calculation of The
Power Factor Correction?
Calculating the dimensions of the capacitor bank you need to install
in your system is very simple: note the cos of the system without
power factor correction and the cos you want to obtain and it will
take just a few calculations to derive the reactive power necessary in
order to reach the desired power factor. The power factor can differ
greatly between two users because it depends both on the type of
equipment installed and how it is used.
For example, asynchronous motors – by far the most widely used, though
brushless motors actuated by static AC/DC or AC/AC converters have
been gaining popularity in recent years – have a power factor that
varies greatly according to the motor load and type of construction
and can reach very low values in the absence of loads. Similar
observations may be made with respect to transformers. For all these
types of electric machines, recourse is often made to a fixed power
factor correction at the motor or transformer level. Other significant
differences can be seen in electrical equipment such as lamps,
furnaces, welding machines and converters.
Calculating of reactive power necessary power factor correction
P = active power of the system
cosφ0 = cosφ of system without power
factor correction
cosφ1 = cosφ you want to bring the
system to
Qc = reactive power of power factor
correction system to be installed
k =
cosφ0 and
cosφ1, this data is derived from the table
(next page)
Qc = P(tanφ0 - tanφ1)
=P.K
Correcting the Power Factor of MV / LV Transformers
It is always a good idea to ensure a power factor correction for MV /
LV transformers, since even when they are operating loadless (e.g.
during the night) they absorb reactive power, which must be
compensated. The exact capacitor power necessary may be calculated
using the formula below:
Q = Io% * Pn / 100
Io = loadless current (specified by the transformer manufacturer)
Pn = rated power of the transformer
Where alternatively, if the required data is not available, you can
refer to the table below, which differentiates among types of
transformers with NORMAL losses.
Reactive power for CORRECTING the POWER FACTOR CORRECTION NO LOAD of
50hz three phase transformation MV/LV(kvar)

|
|
 |
Real Time Power Factor
Correction (Activcomp) and What are Its Advantages ?
General information
Modern manufacturing plants are characterized by the use of highly
dynamic machinery, like welding loads. Alongside the undisputed
advantages of today’s modern techniques there is however the
disadvantage that the mains supply networks are often affected by
frequent load fluctuations and harmonic oscillation. It often leads to
unstable stress ratios. Flickering, excessive current and increased
losses in energy distribution. This reduces not only the supply
capacity but also impairs the function of sensitive electronics
controls.
Conventional reactive power compensation systems are designed for
optimizing the power factor and reducing the level of harmonic
oscillation, but offer no satisfactory solution for frequent load
fluctuations. The range of application of these units is the
compensation of static as well as fluctuating loads with switching
cycles measured by minutes.
|
ACTIVCOMP
|
- At each moment optimized
cosφ
- Soft switching without transients
- Flicker eliminated
|
Application
|
|
The real-time power factor compensation equipment of series
Activcomp
offers a solution. In these assemblies the classic components
controller and air contactor are substituted by a combination of
corresponding high speed controller and thyristor power modules type
Activcomp . This
system reacts immediately on load fluctuation and reactive power
surges will be neutralised in the supply network. The power factor is
optimised at each moment, on cycle to cycle basis, typical response
time less than 20 ms. The negative effects described above are reduced
to a minimum. This gives the consumer not only the advantage of a
stable supply ratio, but the ability to minimise energy distribution
and reduce costs. To increase the switching performance to an optimum,
the control signal for the steering of the capacitor banks can
alternatively be given directly by the logic control of bigger loads.
|
|
|
Coefficient k by which to multiply the active energy consumed in KW
in order to determine the KVAR necessary for correcting the power
factor (Cosφ1 is the initial PF obtainable with
correction),
Recommender final
Cosφ = 0.95 upto1.00
|
| Coefficient
K |
| Value |
Cosφ |
|
Tgφ |
Cosφ |
0.85 |
0,86 |
0,87 |
0,88 |
0,89 |
0,90 |
0,91 |
0,92 |
0,93 |
0,94 |
0,95 |
0,96 |
0,97 |
0,98 |
0,99 |
1,00 |
| 3,18 |
0,30 |
2,560 |
2,586 |
2,613 |
2,640 |
2,667 |
2,695 |
2,754 |
2,754 |
2,785 |
2,817 |
2,851 |
2,888 |
2,929 |
2,977 |
3,037 |
3,180 |
| 3,0 |
0,31 |
2,447 |
2,474 |
2,500 |
2,527 |
2,555 |
2,583 |
2,611 |
2,641 |
2,672 |
2,704 |
2,738 |
2,775 |
2,816 |
2,864 |
2,924 |
3,067 |
| 2,96 |
0,32 |
2,341 |
2,367 |
2,394 |
2,421 |
2,448 |
2,476 |
2,505 |
2,535 |
2,565 |
2,598 |
2,632 |
2,669 |
2,710 |
2,758 |
2,818 |
2,961 |
| 2,86 |
0,33 |
2,241 |
2,267 |
2,294 |
2,321 |
2,348 |
2,376 |
2,405 |
2,435 |
2,465 |
2,498 |
2,532 |
2,569 |
2,610 |
2,657 |
2,718 |
2,861 |
| 2,77 |
0,34 |
2,146 |
2,173 |
2,199 |
2,226 |
2,254 |
2,282 |
2,310 |
2,340 |
2,371 |
2,403 |
2,437 |
2,474 |
2,515 |
2,563 |
2,623 |
2,766 |
| 2,68 |
0,35 |
2,057 |
2,083 |
2,110 |
2,137 |
2,164 |
2,192 |
2,221 |
2,250 |
2,281 |
2,313 |
2,348 |
2,385 |
2,426 |
2,473 |
2,534 |
2,676 |
| 2,59 |
0,36 |
1,972 |
1,998 |
2,025 |
2,052 |
2,079 |
2,107 |
2,136 |
2,166 |
2,196 |
2,229 |
2,263 |
2,300 |
2,341 |
2,388 |
2,449 |
2,592 |
| 2,51 |
0,37 |
1,891 |
1,918 |
1,994 |
1,971 |
1,999 |
2,027 |
2,055 |
2,085 |
2,116 |
2,148 |
2,187 |
2,219 |
2,260 |
2,308 |
2,368 |
2,511 |
| 2,43 |
0,38 |
1,814 |
1,841 |
1,867 |
1,894 |
1,922 |
1,950 |
1,979 |
2,008 |
2,039 |
2,071 |
2,105 |
2,143 |
2,184 |
2,231 |
2,292 |
2,434 |
| 2,36 |
0,39 |
1,741 |
1,768 |
1,794 |
1,821 |
1,849 |
1,877 |
1,905 |
1,935 |
1,966 |
1,998 |
2,032 |
2,069 |
2,110 |
2,158 |
2,219 |
2,361 |
| 2,29 |
0,40 |
1,672 |
1,698 |
1,725 |
1,752 |
1,779 |
1,807 |
1,836 |
1,865 |
1,896 |
1,928 |
1,963 |
2,000 |
2,041 |
2,088 |
2,149 |
2,291 |
| 2,22 |
0,41 |
1,605 |
1,631 |
1,658 |
1,685 |
1,712 |
1,740 |
1,796 |
1,799 |
1,829 |
1,862 |
1,896 |
1,933 |
1,974 |
2,022 |
2,082 |
2,225 |
| 2,16 |
0,42 |
1,514 |
1,567 |
1,594 |
1,621 |
1,648 |
1,676 |
1,705 |
1,735 |
1,766 |
1,798 |
1,832 |
1,869 |
1,910 |
1,958 |
2,018 |
2,161 |
| 2,10 |
0,43 |
1,480 |
1,506 |
1,533 |
1,560 |
1,587 |
1,615 |
1,644 |
1,674 |
1,704 |
1,737 |
1,771 |
1,808 |
1,849 |
1,897 |
1,957 |
2,100 |
| 2,04 |
0,44 |
1,421 |
1,448 |
1,474 |
1,501 |
1,526 |
1,557 |
1,585 |
1,615 |
1,646 |
1,678 |
1,712 |
1,749 |
1,790 |
1,838 |
1,898 |
2,041 |
| 1,98 |
0,45 |
1,365 |
1,391 |
1,418 |
1,445 |
1,472 |
1,500 |
1,529 |
1,559 |
1,589 |
1,622 |
1,656 |
2,693 |
1,734 |
1,781 |
1,842 |
1,985 |
| 1,93 |
0,46 |
1,311 |
1,337 |
1,364 |
1,391 |
1,418 |
1,446 |
1,475 |
1,504 |
1,535 |
1,567 |
1,602 |
1,639 |
1,680 |
1,727 |
1,788 |
1,930 |
| 1,88 |
0,47 |
1,258 |
1,285 |
1,311 |
1,338 |
1,366 |
1,394 |
1,422 |
1,452 |
1,483 |
1,515 |
1,549 |
1,.586 |
1,627 |
1,675 |
1,736 |
1,878 |
| 1,83 |
0,48 |
1,208 |
1,234 |
1,261 |
1,288 |
1,315 |
1,343 |
1,372 |
1,402 |
1,432 |
1,456 |
1,499 |
1,536 |
1,577 |
1,625 |
1,685 |
1,828 |
| 1,78 |
0,49 |
1,159 |
1,189 |
1,212 |
1,239 |
1,267 |
1,295 |
1,323 |
1,353 |
1,384 |
1,416 |
1,450 |
1,487 |
1,528 |
1,576 |
1,637 |
1,779 |
| 1,73 |
0,50 |
1,112 |
1,139 |
1,165 |
1,192 |
1,220 |
1,248 |
1,276 |
1,306 |
1,337 |
1,369 |
1,403 |
1,440 |
1,481 |
1,529 |
1,590 |
1,732 |
| 1,69 |
0,51 |
1,067 |
1,093 |
1,120 |
1,147 |
1,174 |
1,202 |
1,231 |
1,261 |
1,391 |
1,324 |
1,358 |
1,395 |
1,436 |
1,484 |
1,544 |
1,687 |
| 1,64 |
0,52 |
1,023 |
1,049 |
1,079 |
1,103 |
1,130 |
1,158 |
1,187 |
1,217 |
1,247 |
1,280 |
1,314 |
1,351 |
1,392 |
1,440 |
1,500 |
1,643 |
| 1,60 |
0,53 |
0,980 |
1,007 |
1,033 |
1,060 |
1,088 |
1,116 |
1,144 |
1,174 |
1,205 |
1,237 |
1,271 |
1,308 |
1,349 |
1,397 |
1,458 |
1,600 |
| 1,56 |
0,54 |
0,939 |
0,965 |
0,992 |
1,019 |
1,046 |
1,074 |
1,103 |
1,133 |
1,163 |
1,196 |
1,230 |
1,267 |
1,308 |
1,356 |
1,416 |
1,556 |
| 1,52 |
0,55 |
0,899 |
0,925 |
0,952 |
0,979 |
1,006 |
1,034 |
1,063 |
1,092 |
1,123 |
1,156 |
1,190 |
1,227 |
1,268 |
1,315 |
1,376 |
1,518 |
| 1,48 |
0,56 |
0,860 |
0,886 |
0,913 |
0,940 |
0,967 |
0,995 |
1,024 |
1,053 |
1,084 |
1,116 |
1,151 |
1,188 |
1,229 |
1,276 |
1,337 |
1,476 |
| 1,44 |
0,57 |
0,822 |
0,848 |
0,875 |
0,902 |
0,926 |
0,957 |
0,986 |
1,015 |
1,046 |
1,079 |
1,113 |
1,150 |
1,191 |
1,.238 |
1,299 |
1,441 |
| 1,40 |
0,58 |
0,785 |
0,811 |
0,838 |
0,865 |
0,892 |
0,920 |
0,949 |
0,979 |
1,009 |
1,042 |
1,076 |
1,113 |
1,154 |
1,201 |
1,262 |
1,405 |
| 1,37 |
0,59 |
0,749 |
0,775 |
0,802 |
0,829 |
0,56 |
0,884 |
0,913 |
0,942 |
0,973 |
1,006 |
1,040 |
1,077 |
1,118 |
1,165 |
1,226 |
1,368 |
| 1,33 |
0,60 |
0,714 |
0,740 |
0,767 |
0,794 |
0,821 |
0,849 |
0,878 |
0,907 |
0,938 |
0,970 |
1,005 |
1,042 |
1,083 |
1,130 |
1,191 |
1,333 |
| 1,30 |
0,61 |
0,679 |
0,706 |
0,732 |
0,759 |
0,787 |
0,815 |
0,843 |
0,873 |
0,904 |
0,936 |
0,970 |
1,007 |
1,048 |
1,096 |
1,157 |
1,299 |
| 1,27 |
0,62 |
0,646 |
0,672 |
0,699 |
0,726 |
0,753 |
0,781 |
0,810 |
0,839 |
0,870 |
0,903 |
0,937 |
0,374 |
1,015 |
1,062 |
1,123 |
1,265 |
| 1,23 |
0,63 |
0,613 |
0,639 |
0,666 |
0,693 |
0,720 |
0,748 |
0,777 |
0,807 |
0,837 |
0,870 |
0,904 |
0,941 |
0,982 |
1,030 |
1,090 |
1,233 |
| 1,20 |
0,64 |
0,581 |
0,607 |
0,634 |
0,661 |
0,688 |
0,.716 |
0,745 |
0,775 |
0,805 |
0,838 |
0,872 |
0,909 |
0,950 |
0,998 |
1,058 |
1,201 |
| 1,17 |
0,65 |
0,549 |
0,579 |
0,602 |
0,629 |
0,657 |
0,685 |
0,714 |
0,743 |
0,774 |
0,806 |
0,840 |
0,877 |
0,919 |
0,966 |
1,027 |
1,169 |
| 1,14 |
0,66 |
0,519 |
0,545 |
0,572 |
0,599 |
0,626 |
0,654 |
0,683 |
0,712 |
0,743 |
0,775 |
0,810 |
0,847 |
0,888 |
0,935 |
0,996 |
1,138 |
| 1,11 |
0,67 |
0,488 |
0,515 |
0,541 |
0,568 |
0,596 |
0,624 |
0,652 |
0,682 |
0,713 |
0,.745 |
0,779 |
0,816 |
0,857 |
0,905 |
0,966 |
1,108 |
| 1,08 |
0,68 |
0,459 |
0,485 |
0,512 |
0,539 |
0,566 |
0,594 |
0,623 |
0,652 |
0,683 |
0,715 |
0,750 |
0,787 |
0,828 |
0,875 |
0,936 |
1,078 |
| 1,05 |
0,69 |
0,429 |
0,456 |
0,482 |
0,509 |
0,537 |
0,565 |
0,593 |
0,623 |
0,654 |
0,686 |
0,702 |
0,57 |
0,798 |
0,846 |
0,907 |
1,049 |
| 1,02 |
0,70 |
0,400 |
0,427 |
0,453 |
0,480 |
0,508 |
0,539 |
0,565 |
0,594 |
0,625 |
0,.657 |
0,692 |
0,729 |
0,770 |
0,817 |
0,878 |
1,020 |
| 0,99 |
0,71 |
0,372 |
0,398 |
0,425 |
0,452 |
0,480 |
0,508 |
0,536 |
0,566 |
0,597 |
0,629 |
0,663 |
0,700 |
0,714 |
0,789 |
0,849 |
0,992 |
| 0,96 |
0,72 |
0,344 |
0,370 |
0,397 |
0,424 |
0,452 |
0,480 |
0,508 |
0,538 |
0,569 |
0,601 |
0,635 |
0,672 |
0,713 |
0,761 |
0,821 |
0,964 |
| 0,94 |
0,73 |
0,316 |
0,343 |
0,370 |
0,396 |
0,424 |
0,452 |
0,481 |
0,510 |
0,541 |
0,.573 |
0,608 |
0,645 |
0,686 |
0,733 |
0,794 |
0,936 |
| 0,91 |
0,74 |
0,289 |
0,316 |
0,342 |
0,369 |
0,397 |
0,425 |
0,453 |
0,483 |
0,514 |
0,546 |
0,580 |
0,617 |
0,658 |
0,706 |
0,766 |
0,909 |
| 0,88 |
0,75 |
0,262 |
0,289 |
0,315 |
0,342 |
0,370 |
0,398 |
0.,426 |
0,456 |
0,487 |
0.,519 |
0,553 |
0,590 |
0,631 |
0,679 |
0,739 |
0,882 |
| 0,86 |
0,76 |
0,235 |
0,262 |
0,288 |
0,315 |
0,343 |
0,371 |
0,400 |
0,429 |
0,460 |
0,492 |
0,526 |
0,563 |
0,605 |
0,652 |
0,713 |
0,855 |
| 0,83 |
0,77 |
0,209 |
0,235 |
0,262 |
0,289 |
0,316 |
0,344 |
0,373 |
0,403 |
0,433 |
0,466 |
0,500 |
0,537 |
0,578 |
0,626 |
0,686 |
0,829 |
| 0,80 |
0,78 |
0,183 |
0,209 |
0,236 |
0,263 |
0,290 |
0,318 |
0,347 |
0,376 |
0,407 |
0,439 |
0,474 |
0,511 |
0,552 |
0,599 |
0,660 |
0,.802 |
| 0,78 |
0,79 |
0,156 |
0,183 |
0,209 |
0,236 |
0,264 |
0,292 |
0,320 |
0,350 |
0,381 |
0,413 |
0,447 |
0,484 |
0,525 |
0,573 |
0,634 |
0,776 |
| 0,75 |
0,80 |
0,130 |
0,157 |
0,183 |
0,210 |
0,238 |
0,266 |
0,294 |
0,324 |
0,355 |
0,387 |
0,421 |
0,458 |
0,499 |
0,547 |
0,608 |
0,750 |
| 0,72 |
0,81 |
0,104 |
0,131 |
0,157 |
0,184 |
0,212 |
0,240 |
0,268 |
0,298 |
0,329 |
0,361 |
0,395 |
0,432 |
0,473 |
0,521 |
0,581 |
0,724 |
| 0,70 |
0,82 |
0,078 |
0,105 |
0,131 |
0,158 |
0,186 |
0,214 |
0,242 |
0,272 |
0,303 |
0,335 |
0,369 |
0,406 |
0,447 |
0,495 |
0,556 |
0,698 |
| 0,67 |
0,83 |
0,052 |
0,079 |
0,105 |
0,132 |
0,160 |
0,188 |
0,216 |
0,246 |
0,277 |
0,309 |
0,343 |
0,380 |
0,421 |
0,469 |
0,530 |
0,672 |
| 0,65 |
0,84 |
0,029 |
0,053 |
0,079 |
0,106 |
0,134 |
0,162 |
0,190 |
0,220 |
0,251 |
0,283 |
0,317 |
0,354 |
0,395 |
0,443 |
0,503 |
0,646 |
| 0,62 |
0,85 |
|
0,026 |
0,053 |
0,080 |
0,107 |
0,135 |
0,164 |
0,194 |
0,225 |
0,257 |
0,291 |
0,328 |
0,369 |
0,417 |
0,477 |
0,620 |
| 0,59 |
0,86 |
|
|
0,027 |
0,054 |
0,081 |
0,109 |
0,138 |
0,167 |
0,198 |
0,230 |
0,265 |
0,302 |
0,343 |
0,390 |
0,451 |
0,593 |
| 0,57 |
0,87 |
|
|
|
0,027 |
0,054 |
0,082 |
0,111 |
0,141 |
0,172 |
0,204 |
0,238 |
0,275 |
0,316 |
0,364 |
0,424 |
0,567 |
| 0,54 |
0,88 |
|
|
|
|
0,027 |
0,055 |
0,084 |
0,114 |
0,145 |
0,177 |
0,211 |
0,248 |
0,289 |
0,337 |
0,397 |
0,540 |
| 0,51 |
0,89 |
|
|
|
|
|
0,028 |
0,057 |
0,086 |
0,117 |
0,149 |
0,184 |
0,221 |
0,262 |
0,309 |
0,370 |
0,512 |
| 0,48 |
0,90 |
|
|
|
|
|
|
0,029 |
0,058 |
0,089 |
0,121 |
0,156 |
0,193 |
0,234 |
0,281 |
0,342 |
0,484 |
| 0,46 |
0,91 |
|
|
|
|
|
|
|
0,030 |
0,060 |
0,093 |
0,127 |
0,.164 |
0,205 |
0,253 |
0,313 |
0,456 |
| 0,43 |
0,92 |
|
|
|
|
|
|
|
|
0,031 |
0,063 |
0,097 |
0,134 |
0,175 |
0,223 |
0,284 |
0,426 |
| 0,46 |
0,93 |
|
|
|
|
|
|
|
|
|
0,032 |
0,067 |
0,104 |
0,145 |
0,192 |
0,253 |
0,395 |
| 0,36 |
0,94 |
|
|
|
|
|
|
|
|
|
|
0,034 |
0,071 |
0,.112 |
0,160 |
0,220 |
0,363 |
| 0,33 |
0,95 |
|
|
|
|
|
|
|
|
|
|
|
0,037 |
0,078 |
0,126 |
0,186 |
0,329 |
| 0,29 |
0,96 |
|
|
|
|
|
|
|
|
|
|
|
|
0,041s |
0,089 |
0,149 |
0,292 |
| 0,25 |
0,97 |
|
|
|
|
|
|
|
|
|
|
|
|
|
0,048 |
0,108 |
0,251 |
| 0,20 |
0,98 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
0,061 |
0,203 |
| 0,14 |
0,99 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
0.142 |
|
|
Advantages of Thyristor Switched Over Electro-Mechanical
Compensation System ?
|
|
Fast and Accurate Compensation
The Activcomp is a Transient Free Fast Compensation System. It is used
for Power Factor Correction & Harmonic Filter. The compensation is
based on averaging the FFT analysis of each cycle, resulting in more
accurate compensation, even in the presence of harmonics.
Simultaneous Group Connection
When load changes require connection or disconnection of more than one
step, the Activcomp controls the switching of as many steps as
required at precisely the same time. Simultaneous connection or
disconnection provides the following benefits :
• Fast full compensation.
• For Eg., with 1:2:2 system configuration and groups 1 & 2 are
connected. When 1 more step is required, group 3 will
be connected
simultaneously while group 1 is disconnected.
• Real binary sizing - 1:2:2 is exactly the same as 1:1:1:1:1.
Transient-free Switching
Electronic switching technology prevents any transients typically
associated with conventional capacitor switching. This is extremely
important in sites with sensitive electronic equipment, such as
hospitals, data centers and facilities.
Fixed Capacity & Filter Characteristics
The capacity of the Activcomp capacitors is virtually permanent over
the years, which prevents the need to replace capacitors. Moreover the
tuning frequency remains constant over time, which allows system
performance to remain at the highest possible level.
There is an ongoing cumulative reduction of capacity in electro
mechanically switched PFC systems due to the effect of transients
during connections and disconnection. This can be detrimental to
detuned electro mechanically switched systems where the changes in
ratio between the capacitors/reactors shift the resonance frequency,
which may result in resonance. The Activcomp prevents these
conditions.
Long Life and Reduced Maintenance Costs
Neptune Activcomp reduces site maintenance costs by increasing the
lifetime of:
• Switching elements
• Capacitors
• Sensitive electronic equipment
Capacitor Duty Cycle-SCAN Mode
The unique SCAN feature protects the Activcomp’s capacitors &
reactors, increases their life span. Simultaneous connection and
disconnection of steps in FIFO (First In First Out) manner is shown in
diagram on the previous page.
The scan feature reduces the average current in the capacitors and the
reactors and therefore providing the following advantages:
• Reduces substantially the increase of temperature in these elements
resulting in longer life expectancy of the
inductors and capacitors.
• Reduces the effect of over-current and over voltage caused by the
harmonics on the capacitors and inductors.
• The tuning frequency of the de-tuned filter or tuned filter is
stable due to the fact that the capacitor value (micro farad)
doesn't
change due to the low temperature achieved by the scan mode.
Easy to Use and Maintain
The advanced DSP and microprocessor-based controller, with its large
full graphic LCD display, provides easy-to-use operation. The
controller includes a complete electrical measurement system, which
can replace a facilities main monitoring meter. The controller
operates the BIT (Built In Test), which reports system or network
conditions. The optional PowerlQ software can remotely control all
Activcomp operation and display additional system power information.
|
|
 |
Power Factor Corrections Capacitors.
Unlike most electrical equipment, power factor correction capacitors,
each time they are energized, continuously operate at full load or at
loads which differ from this value only as a consequence of variations
in voltage and frequency.
Overstressing and overheating shorten the life span of the capacitor.
For this reason the operating conditions (temperature, voltage and
current) must be carefully controlled in order to obtain optimum
results as respects the lifespan of the capacitor.
Voltage
The capacitors are produced in accordance with reference standards EN
60831-1/2 which regulate their manufacturing, testing, installation
and application and which indicate the following maximum values for
over voltage applicable to the capacitors:
+10% for 8 hours every 24 hours
+15% for 30 minutes every 24 hours |
+20% for 5 minutes every 24 hours
+30% for 1 minute every 24 hours. |
Over voltages in excess of 15% should not occur more than 200 times in
the lifespan of the capacitor. Often when there is the presence of
overload conditions during service, in the presence of a moderate
harmonic load for example, it is common to use oversized capacitors in
terms of voltage.
|
 |
|
In such cases the output power at operating voltage will be reduced
with respect to that of the rated load. It is advisable to evaluate
the reduction experienced in the output power on the basis of the
correlation between the operating voltage and the rated voltage.
The following table indicates the output power of a 100 kvar capacitor
used on a 400 V network with a rated voltage of 450 V, 500 V and 550 V.
|
| Un |
450 |
500 |
550 |
| Q output kvar
|
79 |
64 |
53 |
|
|
Temperature
The temperature of the capacitor during operation is the parameter
that, along with the voltage, has the greatest influence on the life
span of the capacitor. It is important that the capacitor always be
placed in a position where the cooling air can freely circulate,
avoiding the radiant heat of hot surfaces of other components. When
the capacitors are placed in closed cabinets it is necessary to have
air vents which allow for an easy exchange of air between the interior
and exterior of the cabinet. On the other hand, when the degree of
protection of the cabinet does not permit this exchange of air, the
internal spaces must be much larger and the positioning of the
capacitors must be carefully studied to permit the necessary channels
which allow for the circulation of cooling air. In this case the
forced cooling air will have to be provided by suitable fans. As a
rule the temperature of the cooling air inside the cabinet should not
differ by more than 5ºC with respect to the external air at the
control panel.
Cooling air temperature
This is the temperature of cooling air measured at the hottest point
of the bank of capacitors, under working conditions, halfway between
two capacitors or on the surface of one of these.
Categories of ambient air temperature
This represents the range of cooling air temperatures in which the
capacitor is designed to operate. As a rule there are 4 categories
represented by a number and a letter or by two numbers as shown in the
table.
|
|
Categories |
Ambient air temperature |
| |
|
Max |
|
Highest mean
over any period of |
|
24h |
1year |
|
| -25/A |
-25+40°C. |
40 |
40 |
40 |
| -25/B |
-25+45°C |
45 |
35 |
35 |
| -25/c |
-25+50°C |
50 |
40 |
40 |
| -25/D |
-25+55°C |
55 |
45 |
35 |
|
|
The first number represents the minimum temperature of the cooling air
at which the capacitor can be energized (-25ºC) on request -40ºC. The
letter or the second number represents the upper limit of the
temperature range and precisely the max. value indicated in the table.
Residual voltage
This is the voltage that remains after disconnecting the capacitor
from the network. This voltage must be eliminated in order to avoid
dangerous conditions for the operator. All three-phase capacitors are
equipped with discharge devices, that reduce the residual voltage to a
value of minimum 75 V after 3 minutes.
It is important to bear in mind that the capacitors cannot be
energized if there is a residual voltage of more than 10% across them.
Particular attention must therefore be applied in harmonizing the
capacitor discharge times with the response times of the control
devices (Regulators). In cases where the lag time of the regulators
are shorter than the discharge time of the capacitor, it is necessary
to provide additional discharge devices until the connection occurs
with a residual voltage of less than 10%.
To reduce the residual voltage to 50 V in 20 seconds in batteries with
a power less than or equal to 20 kvar at a voltage of 400 V, use 3
metal oxide resistors of 68 kohm, 4W in a delta connection.
Max current
The capacitors are made to function conforming to standards EN 60831 -
1/2 continuously at an effective value at last of 1.3 times the value
of the current at rated voltage and frequency. Bearing in mind the
capacitance tolerance, the maximum current can arrive to 1.5 In, the
value to which it is necessary to refer in the scaling of the line of
control and protection devices. This overcurrent factor can be
determined by the
combined effect of harmonics, overvoltages and capacitance tolerance.
Max inrush current
Transient overcurrents having elevated amplitudes and high frequencies
occur when the capacitors are switched in to the circuit. This is
especially true when a bank of capacitors are put in a parallell
connection with other already-energized capacitors. It may therefore
be necessary to reduce these transient overcurrents to acceptable
values both for the capacitor and the contactor used by connecting the
capacitor using suitable devices (resistors or reactors) in the power
circuit of the battery. The peak value of the overcurrent caused
during maneuvering operations must be limited to a maximum value of
100 In (crest
value of the 1st cycle).
|
|
|
 |
Harmonics in electrical system results in wave form distortion. In
general harmonics are periodic disturbances in voltage and current.
Any non-sinusoidal periodic wave form can be considered as combination
of sine waves of certain frequencies, amplitudes and phase angle (fourier
series). In simple terms Harmonics are multiple of the normal main
power frequency, like "3rd order" harmonics has got frequency of 150
Hz and "5th order" has to 250 Hz frequency. Harmonics causes pollution
in electrical systems, which may affect the equipment at much larger
distances from origin and if not controlled can become expensive
preposition.
In a wave shape only the fundamental component of voltage and current
contribute to power translation. The harmonics only load the
translation system and cause increase in apparent power of source.
This non-active power due to harmonics is referred as distortion
power.
Power factor correction capacitor banks of such loads are put under
considerable stress by presence of harmonics.
|
|

|
|
|
Harmonics are not generated by power generators
but are produced by non-linear loads which can be one of the
following:-
Loads that make use of semi conductor devices like transistor,
thyristor i.e. static rectifiers.
(AC/DC conversation using SCRs), static frequency converters,
static inverters
like :
|
 |
|
Figure |
|
- Static power converters (AC-DC conversion using
SCRs)
- Static rectifiers
- Static frequency convertor
- Static uninterruptible power supplies
- Static induction regulators.
|
-
Variable impedance loads, using electric arcs, arc furnaces,
welding units, fluorescent tubes, discharge lamps, Light control,
brightness etc.
-
Loads using strong magnetising currents saturated Transformer,
inductance furnaces, reactors etc.
- Office automation products like computers, UPS, printers and fax
machine etc.
A non-linear load is a load for which the current consumption does not
reflect the supply voltage although the load voltage source is
sinusoidal, the current consumption is not sinusoidal.
High level of harmonic distortion can create stress and resultant
problems for the utility's distribution system, the plant's
distribution system, as well as the plants equipment. Equipment
shutdown can result from too-high levels of harmonic distortion.
Following is the list of problems that enhanced harmonic distortion
can create :
-
The capacitors are subjected to a voltage overload and their
lifetime is drastically reduced; in fact the voltage drop across the
capacitor caused by each of the harmonic currents present must be
added to the fundamental voltage. This over voltage is well above
10% when resonance is present, causing the premature dielectric
breakdowns.
- Connection of the cap. causes a large increase in the voltage
distortion factor THD(V).
- Motors; Reduced motor life, inability to fully load motor.
-
The user
transformers, wires and loads are affected by this increase in
current, which leads to increased I2
R losses and eddy current losses in transformer. This reduces the
capacity of transformer resulting into economic loss as well.
Apart from this transformer may also be subjected to excessive
overheating and saturation.
This will shorten the life or
transformer. When transformer fails, the cost of loss of
productivity during emergency repair time far exceeds the
replacement cost of transformer itself.
-
Interference in computers, microprocessor & solid state
controlled equipment because of distorted 240 V supply. Increased
neutral to ground voltage may cause hardware problems which may
initially look like software problem. International standards
recommend that voltage distortion for computer use be limited to
maximum of 5% total harmonic distortion (THD-V) and the largest
single harmonic not to exceed 3%.
-
High voltage distortion shall also be encountered when shifting
from mains to emergency generator as they offer high impedance than
supply transformer.
- Random switching in deferential relays.
-
Large current in neutral wires of power distribution system.
This is a real fire hazard as usually phase wires are protected by
circuit breakers or fuses.
-
Poor power factor: As mentioned earlier the harmonic current
caused by non-linear loads do not carry any real power (KW) even
though they do increase the volt amperage (KVA). This lowers the
power factor at (Pf=KW/KVA) the main distribution transformer.
Utilities put penalties on consumers with low p.f, less than 0.9.
-
Over heating in fuses resulting in false blowing. False /
spurious operations of breakers, which may lead to variation in
other characteristics.
-
Higher rotation speed of the disks in energy counters due to
additional torque resulting in measurement errors.
- Reduction of power generated by UPS.
-
Communication / Telephone circuit interference because of
induced harmonic noise.
|
 |
 |
Standards define a Harmonic as “one of the components obtained from
the breakdown of a periodic wave (voltage or current) in the Fourier
Series”. The order of a harmonic is further defined as “the ratio
between the frequency of a harmonic and the fundamental frequency of
the network”.
Power converters are being used more and more frequently in plants to
control motors, medium-frequency ovens, uninterruptible power
supplies, etc. These devices regulate the load by modulating the
supply voltage, which results in the generation of current harmonics.
As they circulate through equivalent impedances in the cables and
mains, these harmonics distort the sine waveform of the supply
voltage.
Characteristic harmonics are defined as “those harmonics produced by
static ac/dc converters in ideal theoretical operation”.
The order h of characteristic harmonics is h=mp±1
where m is an integer other than 0 (thus 1, 2, 3, 4, ...) and p is the
number of solid-state switches of the bridge. Therefore, a converter
with six-phase reaction (p=6) generates characteristic harmonics of
the 5th and 7th order (m=1), 11th and 13th order (m=2), 17th and 19th
order (m=3), etc., whereas a converter with twelvephase reaction
(p=12) generates characteristic harmonics of the 11th and 13th order
(m=1), 23rd and 25th order (m=2), etc. Noncharacteristic Harmonics
are
defined as “the harmonics produced:
- by an unbalance in the energy network;
- by an asymmetric delay in the triggering angle of the converter;
- by non-linear devices (frequency changers, fluorescent lamps,
arc furnaces, electric welders, saturations, …)”.
The parameter used to determine the level of harmonic distortion
presents in an electrical network is THD% (Total Harmonic Distortion),
defined as:
|
|
|
|
Where I1 is the effective value of
the fundamental and k represents the effective values of harmonics of
order k.
Due to the current harmonics created by power converters, other
parallel loads in the system are also supplied with a distorted
voltage: this may cause malfunctioning, especially in electronic parts.
The circulation of current harmonics in the system results in
increased losses due to the Joule effect and the effect in the cables,
increased hysteretic losses and increased losses due to parasite
currents in the iron of transformers and motors.
Installing power factor correction capacitors in the network serves to
create a condition of parallel resonance between the equivalent
capacitance of the capacitors and the equivalent inductance of the
system (which may usually be approximated by calculating the
equivalent inductance of the transformer) in correspondence to a
frequency fr.
Where Scc indicates the short circuit power of the system (expressed
in MVA) at the point where the capacitors are connected and Q is the
installed reactive power (expressed in Mvar), the parallel resonance
frequency fr is thus determined:
|
|
|
|
The short circuit power Scc of the system may be approximated by
calculating the short circuit power of the MV/LV transformer,
indicated as Scct, which is given as:
|
|
|
|
where A is the rated power of the transformer (expressed in MVA) and
Vcc% is the percentage short circuit voltage of the transformer.
The voltage harmonics present in the system - having a frequency close
to the parallel resonance frequency fr - may be amplified even
hundreds or thousands of times. For this reason, an extremely high
voltage comes to be created at the capacitor terminals, which causes
the dielectric to age rapidly and hence significantly shortens the
lifespan of the capacitor. For the power factor solution to be adopted
in such cases, refer to the guidelines for choosing shown in the table
on page 1(Criteria for choosing equipment according to plant
requirements).
|
 |
 |
In an industrial plant containing power factor correction capacitors,
harmonics distortions can be magnified due to the interaction between
the capacitors and the service transformer. This is referred to as
harmonic resonance or parallel resonance. It is important to note that
capacitors themselves are not main cause of harmonics, but only
aggravate potential harmonic problems. Often, harmonic-related
problems do not show up until capacitors are applied for power factor
correction.
|
 |
 |
Impedance of the capacitor decreases with increase in frequency.
Capacitor capacity to cancel out harmonic decreases with increase in
frequency. This offer the low impedance path to harmonic currents.
These harmonic currents added to the fundamental current of capacitors
can produce dangerous current overloads on capacitor.
Each of the harmonic currents causes the voltage drop across the
capacitor. This voltage drop is added to the fundamental voltage. Thus
in presence of harmonics higher voltage rating of capacitor is
recommended. This over voltage can be much above permissible 10% value
when resonance is present.
Another important aspect is resonance which can occur when p.f.
capacitors forms the series or parallel resonant circuit with
impedance of supply transformer. If the resonance frequency of this LC
circuit coincides with one of the harmonic present, the amplitude of
the harmonic current flowing through LC circuit is multiplied several
times damaging the capacitors ,supply transformer and other network
components.
It is nor uncommon to find multiplication coefficient K of 5-10 and
over, but in particular operating condition is beyond all control.
|
|
|
Effect of harmonics on capacitors:
|
- Decrease in capacitors reactance


The capacitor reactance
is inversely proportional to the frequency, its curve is reciprocal
and its capacity to cancel out harmonic currents decreases
significantly when the frequency increases.
- Parallel resonance or anti-resonance between capacitors and source
|
-
The reactance of the source Xlt
is proportion to
frequency.
-
The reactance of the capacitors Xc is inesely proportion
to frequency At the frequency Fr.P, there is parallel resonance or
anti-resonance (since the two reactance are equal but opposite)
and amplification (F.A) of the harmonic current in the capacitors
and in the source (transformer) where:
|
it is importance to note that :
|
- The higher the source short-circuit power (Scc.) the further the
resonance is from dangerous harmonic frequencies
- The higher the load power (P), the lower the harmonic current
amplication factor is.
|
 |
Harmonic Filter
Utilities generate an almost perfect sinusoidal voltage. Harmonics,
created by nonlinear loads such as variable speed drives, power
rectifiers, invertors etc., cause non-linear voltage drops and change
the sinusoidal nature of the voltage. When reactive energy is
compensated using capacitors, there is a frequency at which the
capacitors are in parallel resonance with the power source (high
impedance). If the resonant frequency occurs in proximity to one of
the harmonic sources, current can circulate between the supply and the
capacitors, resulting in high voltage on the line. In this scenario,
current levels may exceed the capacitor’s rated current by more than
two or three times, and can cause transformer burn. Resonance can
occur at any frequency, however in most cases, current harmonic
sources exist at the 5th, 7th, 11th, & 13th harmonic. With Activcomp
to cope with Harmonics following solutions can be offered.
De-tuned Systems
In de-tuned systems, reactors are installed in
series with the capacitors and prevent resonance conditions by
shifting the capacitor/network resonance frequency below the first
dominant harmonic (usually the 5th). The graph on the next page shows
the capacitor/network amplification factor and the shifting of the
resonance frequency from near the 5th harmonic to near the 3rd
harmonic.
|
|
|
|
Tuned Systems
If Harmonic Filter is needed, on top of resonance
prevention, tuned reactors are applied. The capacitor/reactor filter
is tunedto absorb particular harmonic and reduce the Total Harmonic
Distortion (THD). The bottom graph on the left shows harmonic
filtration using tuned system: the voltage THD was reduced by more
than 70% (8.8% to 2.5%) and the dominant harmonics (5th and 11th) were
reduced by 75%.
Tuned Activcomp vs. Active Harmonic Filters
Active filters inject currents to the network in anti-phase to the
harmonics. This technology is an expensive solution, and increases
system losses (3% typical). For applications with one or two dominant
harmonics, Neptune’s Tuned Activcomp is the preferred choice, both
technically and economically, effectively minimizing system losses and
reducing the Total Harmonic Distortion (THD).
Harmonics Theory
Introduction
The term “harmonic” refers to sinusoidal components at a frequency
which is a multiple (2,3,4,5...) of the fundamental.
Harmonic source frequencies (fn) can be
expressed as:
fn=fo (PxN ± 1)
Where:
fo = Fundamental frequency
P = Number of rectifier/switching elements
N=Integer number 1, 2, 3, ....
Example: Six pulse rectifier (P=6)
fn = 5, 7, 11, 13, 17, 19 ...
|
|

|
|
The Problem
When the reactive energy is compensated using
capacitors, there is a frequency at which the capacitors are in
parallel resonance with the mains (high impedance).
If the resonance frequency of the capacitors-mains occurs close to one
of the harmonic sources, the current can circulate between the supply
and the capacitors. This results in high voltage on the line and the
capacitor current may exceed the rated current by more than double or
triple its value.
|
 |
|
The Solution
Resonance can occur on any frequency,
however in most cases the current harmonic sources exist at the 5th,
7th, 11th and 13th harmonic.
The Activcomp custom designed reactors, in series with the capacitors,
prevent resonance by shifting the capacitor / network resonance
frequency below the first dominant harmonic
(usually the 5th)
|
 |
|
The
Results
|
|

|
|
 |
 |
The concept of tuned
filter is to create a lower impedance path,
as compared to that of the source, for
currents at frequencies other than 50 Hz.
The information required for the filter
manufacturing source impedance, pf
information, network voltage, load power
information and harmonic summaries at each
load.
Normally the object of installing the
filter shall fall into one of the following
categories.
1) Power Factor Correction to avoid utility
demand charges,
2) Release of Capacity to unload system
transformers and cables,
3) Compliance with local or international
standards like IEEE-519-.
System impedance is important because it
will determine how big, how many stages, and
how aggressive the filter or filters must be
tuned. If the source is stiff (a small
impedance) than the filters need to be more
aggressively tuned and may require to be
tuned at multiple frequencies (stages) to
meet the project goals. If the system is
weak (a large impedance) than a less
aggressive, single stage filter may be used.
Information required to determine the system
impedance are the three phase fault MVA of
the utility distribution connection and the
kVA and percentage impedance of the step
down transformers. A one-line diagram or
sketch of the power system helps when
multiple transformers are involved, see
Figure.
|
 |
The network
voltage is necessary to size the capacitors.
Low voltage capacitors are commonly
available in India with 415V, 440V, 500V,
550V and 690V ratings. Tuned harmonic
filters consist of a reactor in series with
a capacitor. The series reactor will create
a slightly higher voltage on the capacitor
than that of the line. If the harmonic
current that the filter needs to absorb is
large, this voltage could become excessive
and require the use of a higher voltage
capacitor.
Harmonic data is the most critical
information to be provided. It is important
to take snap-shots of the harmonic spectra
in all of the plant operation
configurations. Ideally, the harmonic
spectra will be trended over several plant
cycles (day, week, month, etc.) To assure
that the largest load has been measured and
to help with reactive power requirements, it
is a good idea to include the past 12 months
of utility bills. If possible, a snap-shot
measurement with minimal plant load will
help determine the amount of utility
distortion that the filter may need to
absorb.
|
 |
 |
There are three
choices when deciding where to apply
harmonic filters:
• At the Load
• At the transformer or
• On the Primary Distribution.
SOLUTIONS
NAAC ENERGY CONTROLS (P) LIMITED can offer
following solutions for mitigation of
Harmonics.
• Detuned Filtration System
• Tuned Filtration System
• Hybrid System • Active Filters
From application to application the
correct choice will differ.
Contact our Corporate Office in Delhi or
Regional Offices for further information
regarding Harmonic Filter or Load / Harmonic
Analysis at your site.
|
|
 |
|
|
|
|
|